MTech’s Addressable Fire Smoke Control System MA-FSCS monitors and controls fire events in a building. The system is commonly used in high-rises, and is designed for firefighters and building maintenance engineers and presents crucial information on the situation of the building during an event. It is also used as part of standard maintenance procedures for integrated systems: HVAC, Smoke and Fire Detection, Low Voltage Systems, Lift and Escalators, Voice and Emergency Evacuation.
MTech’s Addressable Fire Smoke Control System MA-FSCS monitors and controls fire events in a building. The system is commonly used in high-rises, and is designed for firefighters and building maintenance engineers and presents crucial information on the situation of the building during an event. It is also used as part of standard maintenance procedures for integrated systems: HVAC, Smoke and Fire Detection, Low Voltage Systems, Lift and Escalators, Voice and Emergency Evacuation.
Because the panel is used by firefighters with minimal prior knowledge of building-specific layout, its design is simple and intuitive. It contains all the required components that are needed to control a fire event, as well as graphical representations to help decision makers. It is a life safety solution that shares system resources and is therefore more efficient and cost effective than installing multiple interconnected systems.
According to the International Building Code requirements, when a FSCS is activated it gains priority over any other equipment, and controls the event without taking precedence over fire suppression, electrical protection and personnel protection devices. MA-FSCS complies to these requirements.
A typical MA-FSCS with include the following systems, every component is fully customizable:
The MA-FSCS is custom-made by MTech for each client to meet the specific needs of a building, and is manufactured in accordance with ISO 9001:2015 MTech Quality Standard in Four Enclosures compartment:
The system complies with NFPA requirements and is listed by Underwriters Laboratories under the UL864 10th Edition and in the category UUKL for Smoke Management System.
MA-FSCS is also listed as a Firefighter’s Smoke Control Station in high-rise office buildings, malls and other large structures.
MA-FSCS is factory assembled, with switches and LED Indicators wired directly to their respective interface assemblies, eliminating the need for terminal strips and I/O modules and maximizing the number of points that can be included within the enclosure
Includes MA-1000 fire alarm control panel with loop and network card which is mounted inside the enclosure and controls switches and LED Indicators
Includes up to 150 monitoring zones
Monitors up to 400 addressable devises per panel
Utilizes digital output and input type points that interface with the graphic-mounted LED indicators and switches. Typical points include fan on-off control, damper open-close control, fan and damper status, and door release functions
Comes with a loop-check function which scans the system for faulty or turned off devices
More than 75 smoke removal directions
Scheduled weekly self-test with automatic fault and maintenance reports
Code | MA-FSCS |
Description | Addressable Fire Smoke Control System |
Standards for panels | UL864 10th Edition, SII1001-2.2, NFPA92:2018 |
Smoke control | Dedicated /nondedicated system, UUKL.S36158 |
Specification | |
Panel Map | Customized per building and UUKL mechanical and smoke management standard |
Panel 3 position switches | Manual, Automatic and OFF |
Panel indication | LED indication of status of work: Manual, Automatic and OFF |
Number of loops | 2 SLC loops class A |
Loop powered outputs | 300 mA power for loop |
I/O Modules | 300 mA power for loop |
Addresses per loop | Up to 200 addressable devices (MA-IOR) per system |
Programming port | USB port for PC communication |
Output ports | RS485 and RS232 |
Network | LNET/RS-485 – for communication with remote annunciator MA-1050A, MA-8FAN and MA-LED CARD |
MA-TCP/IP – network card for TCP/IP network | |
MA-NET network card for RS-485 network for communication up to 64 Fire Alarm Control Panels in network with global correlation matrix | |
Event history | Buffer for 2,000 events with date and time stamp
and 10,000 events in MA-NET card buffer |
Service | Built-in walk test |
Power | |
Input voltage | Input 120VAC 3.2A / 230VAC 1.6A; 50/60Hz |
Operated voltage | 24VDC 6.5A |
Battery | Two 12V 7 Ah or two 12V 12 Ah (dependent) |
Physical | |
Environmental operating temperature | 0 – 49°C |
Humidity (non-condensing) | 0 – 93% RH |
Physical construction | Metal box |
Ingress protection | IP32 |
Compatibility | |
Suitable for use with | MTech Analog Addressable Fire System |
MTech MB Conventional Fire System | |
MA-1050A Remote Annunciator | |
MA-Monitoring Graphical Management Software |
MA-FSCS
We are forward thinkers and global innovators.
We develop cutting-edge, cost-effective, fire safety solutions to safeguard life and property. We are committed to providing flexible, cutting-edge solutions and support to our clients, at the highest quality and shortest possible turnaround.
Our products are fully compliant with the latest international standards.
© MTech Fire Detection Systems, MTech Fire Detection Systems Ltd is MG company
We are forward thinkers and global innovators.
We develop cutting-edge, cost-effective, fire safety solutions to safeguard life and property. We are committed to providing flexible, cutting-edge solutions and support to our clients, at the highest quality and shortest possible turnaround.
Our products are fully compliant with the latest international standards.
We are forward thinkers and global innovators.
We develop cutting-edge, cost-effective, fire safety solutions to safeguard life and property. We are committed to providing flexible, cutting-edge solutions and support to our clients, at the highest quality and shortest possible turnaround.
Our products are fully compliant with the latest international standards.
© MTech Fire Detection Systems, MTech Fire Detection Systems Ltd is MG company
We will revise your query and get back to you shortly
For signing up to our newsletter
We’ll be in touch soon
For contacting us
We will review your request and get back to you shortly
For submitting your request
We will revise your info and be in touch soon